Skip links

Sarbuz Evaporator

Evaporator Coil
> Copper tubes Ø1/2”,
> Fins made of aluminium,
> Fin spacings are 4-6-8-10 mm,
> Header inlet and outlet tube connections made of copper,
> Admissible pressure Ps=24 Bar.

Casing
> Galvanized steel sheet painted to RAL 9016 (traffic white)

Fans
> Low-noise axial fans with maintenance free motors,
> Protection class IP 44/54, single phase 230V 1~ 50Hz,
> Constructions insulation material class F/B, admissible temperature -30°C up to +40/+55°C,
> In case of long periods of non operation the motors must be operated every month for 2 hours,
> The integral thermo contacts (thermistors) must be used as motor protection,
> At low ambient temperatures and different air resistance the power consumption will increase.

Sound Specifications
> The sound pressure levels are calculated according to EN 13487.

Defrosting

> Electrical defrost as HT for (+2°C/-5°C) or LT type for (–2°C/–25°C) as optional,
> Hot gas defrosts without tubing inside of coil and drip try, without non-return valve,
> Water defrost.

Capacity
> The nominal capacities calculated according to Eurovent (EN329) standards that refer to  SC1-SC2-SC3-SC4 conditions and are valid for R404A,
> The refrigerating capacities refer to an air inlet temperature difference which results from the difference between cooler air inlet temperature Tr, evaporating temperature Te and ΔT = Tr – Te.